Power Cable
Accessories
:
Transition Joints for Screened
Polymeric Insulated Cables
to Screened Paper Insulated 6KV and 10KV |
¡¡ |
¡¡
![](images/poweracc-pic-13.GIF) |
COMPONENTS
1. Connector
2. Yellow Void Filler
3. Oil-resistant Tubing
4. Semi-conductive Tubing
5. Oil-resistant Filler
6. Conductive Breakout
7. Grey Mastic
8. Stress Control Tubing
9. Protective Tubing
10. Insulation/Conductive Tubing
11. Inner Insulation Tubing
12. Metal Case
13. Side Protective Tubing
14. Stress Control Wedge
15. Copper Mesh
16. Earthing Braid
17. Roll Spring
18. Worm Driver Clamp
19. Outer Protective Tubing |
Cables
- The joints are designed for 1-and 3-core
paper Insulated cables to screened 1-or-3-core polymeric insulated
64KV and 10KV.
For Example : YJV, YJLV32, NTSC, N2XSEY, NA2XSEY, N2XSY, NA2XSY,
ZQD, ZLQ, ZQD22, NAKBA, NABA, NKBY
PRODUCT SPECIFICATION
¡¡ |
Ordering
Description |
Type |
Name |
Cross Section (§±) |
4140102130110 |
JSYZ - 10/1x1 |
10KV
1-core
XLPE-PILC
cable
joint |
25-50 |
4140102130210 |
JSYZ - 10/1x2 |
70-120 |
4140102130310 |
JSYZ - 10/1x3 |
150-240 |
4140102130410 |
JSYZ - 10/1x4 |
300-400 |
4140102140110 |
JSYZ - 10/3x1 |
10KV
3-core
XLPE-PILC
cable
joint |
25-50 |
4140102140210 |
JSYZ - 10/3x2 |
70-120 |
4140102140310 |
JSYZ - 10/3x3 |
150-240 |
4140102140410 |
JSYZ - 10/3x4 |
300-400 |
¡¡
Heat-shrinkable
Power Cable Accessories Testing for 10KV XLPE-PILC Cable
¡¡ |
Item
NO |
property |
Test |
Requirements |
Results |
Joint |
1 |
AC withstand for 1min |
GB11033 |
No breakdown and flashover shall
occur at 45kv, 1min |
No breakdown and flashover occurred
on the combi.sample at 45kv, 1min |
OK |
2 |
Load cycle |
GB11033 |
Heating for 5h, cooling for 3h, conductor¡¯s temperature is 65¡É,
3 cycles |
Conductor¡¯s
temperture is 65¡É.
Results refer to the following test |
As left |
3 |
Impulse Voltage withstand 1.2/50us¡¾10times |
GB11033 |
10 positive and 10 negative impulses
at 105KV, Flashover 1time is allowed but not including total testing
times |
No breakdown of the combi.sample
occurred at 105kv |
OK |
4 |
DC voltage withstand negative 15min |
GB11033 |
No breakdown and flashover shall
occur at 52kv |
No breakdown and flashover occurred
on the combi.sample at 52kv, 15min |
OK |
5 |
AC voltage withstand, 4h |
GB11033 |
No breakdown and flashover shall
occur at 35kv, 4h |
No breakdown and flashover occurred
on the combi.sample at 35kv, 4h |
OK |
6 |
Oil-seal up test |
DL413 |
Heating for 24h, cooling for 24h, conductor¡¯s
temperature is 65¡É,
Oil pressure : 100MPa |
Heating for 24h, cooling for 24h, conductor¡¯s temperature is 65¡É,
Oil pressure : 100MPa, No leaking, No seeping |
OK |
![](../OPGW/images/arrow34_N.gif)
¡¡ |
Copyright(c)since 2003 Reliance Corp.
All right reserved
1304, Kumkwang Benesta,1149-2, Jung-Dong, Wonmi-Gu,
Bucheon-city, Gyeonggi-do 420-020, KOREA |
|
|