Power Cable Accessories :
  Transition Joints for Screened Polymeric Insulated Cables
  to Screened Paper Insulated 6KV and 10KV

¡¡

¡¡

COMPONENTS

1. Connector
2. Yellow Void Filler
3. Oil-resistant Tubing
4. Semi-conductive Tubing
5. Oil-resistant Filler
6. Conductive Breakout
7. Grey Mastic
8. Stress Control Tubing
9. Protective Tubing
10. Insulation/Conductive Tubing
11. Inner Insulation Tubing
12. Metal Case
13. Side Protective Tubing
14. Stress Control Wedge
15. Copper Mesh
16. Earthing Braid
17. Roll Spring
18. Worm Driver Clamp
19. Outer Protective Tubing

Cables
  • The joints are designed for 1-and 3-core paper Insulated cables to screened 1-or-3-core polymeric insulated 64KV and 10KV.
    For Example : YJV, YJLV32, NTSC, N2XSEY, NA2XSEY, N2XSY, NA2XSY, ZQD, ZLQ, ZQD22, NAKBA, NABA, NKBY

PRODUCT SPECIFICATION
¡¡

Ordering Description Type Name Cross Section (§±)
4140102130110 JSYZ - 10/1x1 10KV 1-core XLPE-PILC cable joint 25-50
4140102130210 JSYZ - 10/1x2 70-120
4140102130310 JSYZ - 10/1x3 150-240
4140102130410 JSYZ - 10/1x4 300-400
4140102140110 JSYZ - 10/3x1 10KV 3-core XLPE-PILC cable joint 25-50
4140102140210 JSYZ - 10/3x2 70-120
4140102140310 JSYZ - 10/3x3 150-240
4140102140410 JSYZ - 10/3x4 300-400
¡¡

Heat-shrinkable Power Cable Accessories Testing for 10KV XLPE-PILC Cable
¡¡
Item
NO
property Test Requirements Results Joint
1 AC withstand for 1min GB11033 No breakdown and flashover shall occur at 45kv, 1min No breakdown and flashover occurred on the combi.sample at 45kv, 1min OK
2 Load cycle GB11033 Heating for 5h, cooling for 3h, conductor¡¯s temperature is 65¡É, 3 cycles Conductor¡¯s temperture is 65¡É. Results refer to the following test As left
3 Impulse Voltage withstand 1.2/50us¡¾10times GB11033 10 positive and 10 negative impulses at 105KV, Flashover 1time is allowed but not including total testing times No breakdown of the combi.sample occurred at  105kv OK
4 DC voltage withstand negative 15min GB11033 No breakdown and flashover shall occur at 52kv No breakdown and flashover occurred on the combi.sample at 52kv, 15min OK
5 AC voltage withstand, 4h GB11033 No breakdown and flashover shall occur at 35kv, 4h No breakdown and flashover occurred on the combi.sample at 35kv, 4h OK
6 Oil-seal up test DL413 Heating for 24h, cooling for 24h, conductor¡¯s temperature is 65¡É, Oil pressure : 100MPa Heating for 24h, cooling for 24h, conductor¡¯s temperature is 65¡É, Oil pressure : 100MPa, No leaking, No seeping OK

    
¡¡