Power Cable
Accessories
:
Joints for Screen Paper Rubber Insulated Cables
6KV and 10KV |
¡¡ |
Ordering
Description |
Type |
Name |
Cross Section (§±) |
4140102090110 |
JSZ - 10/1x1 |
10KV
1-core
PILC
cable
joint |
25-50 |
4140102090210 |
JSZ - 10/1x2 |
70-120 |
4140102090310 |
JSZ - 10/1x3 |
150-240 |
4140102090410 |
JSZ - 10/1x4 |
300-400 |
4140102120110 |
JSZ - 10/3x1 |
10KV
3-core
PILC
cable
joint |
25-50 |
4140102120210 |
JSZ - 10/3x2 |
70-120 |
4140102120310 |
JSZ - 10/3x3 |
150-240 |
4140102120410 |
JSZ - 10/3x4 |
300-400 |
¡¡
Heat-shrinkable
Power Cable Accessories Testing for 10KV PILC Cable
¡¡ |
Item
NO |
property |
Test |
Requirements |
Results |
Joint |
1 |
AC withstand for 1min |
GB11033 |
No breakdown and flashover shall
occur at 45kv, 1min |
No breakdown and flashover occurred
on the combi.sample at 45kv, 1min |
OK |
2 |
Load cycle |
GB11033 |
Heating for 5h, cooling for 3h, conductor¡¯s temperature is 65¡É,
3 cycles |
Conductor¡¯s
temperture is 65¡É.
Results refer to the following test |
As left |
3 |
Impulse Voltage withstand 1.2/50us¡¾10times |
GB11033 |
10 positive and 10 negative impulses
at 105KV, Flashover 1time is allowed but not including total testing
times |
No breakdown of the combi.sample
occurred at 105kv |
OK |
4 |
DC voltage withstand negative 15min |
GB11033 |
No breakdown and flashover shall
occur at 52kv |
No breakdown and flashover occurred
on the combi.sample at 52kv, 15min |
OK |
5 |
AC voltage withstand, 4h |
GB11033 |
No breakdown and flashover shall
occur at 35kv, 4h |
No breakdown and flashover occurred
on the combi.sample at 35kv, 4h |
OK |
6 |
Oil-seal up test |
DL413 |
Heating for 24h, cooling for 24h, conductor¡¯s
temperature is 65¡É,
Oil pressure : 100MPa |
Heating for 24h, cooling for 24h, conductor¡¯s temperature is 65¡É,
Oil pressure : 100MPa, No leaking, No seelping |
OK |
¡¡ |
Copyright(c)since 2003 Reliance Corp.
All right reserved
1304, Kumkwang Benesta,1149-2, Jung-Dong, Wonmi-Gu,
Bucheon-city, Gyeonggi-do 420-020, KOREA |
|
|