Power Cable
Accessories
:
Joints
for Screen Polymeric or Rubber Insulated Cables
20KV and 35KV |
¡¡ ¡¡ |
Ordering
Description |
Type |
Name |
Cross Section (§±) |
4140103030110 |
JSY - 35/1x01 |
35KV
1-core
XLPE
cable
joint |
50-95 |
4140103030210 |
JSY - 35/1x02 |
120-185 |
4140103030310 |
JSY - 35/1x03 |
240-400 |
4140103060110 |
JSY - 35/3x01 |
35KV
3-core
XLPE
cable
joint |
50-95 |
4140103060210 |
JSY - 35/3x02 |
120-185 |
4140103060310 |
JSY - 35/3x03 |
240-400 |
¡¡
Heat-shrinkable
Power Cable Accessories Testing for 35KV XLPE Cable
¡¡ |
Item
NO |
property |
Test |
Requirements |
Results |
Joint |
1 |
AC withstand for 1min |
GB11033 |
No breakdown and flashover shall
occur at 105kv |
No breakdown and flashover occurred
on the combi.sample at 105kv, 1min |
OK |
2 |
Partial discharge |
GB11033 |
10pC max, at 39KV |
39kV,
¡Â
10pC |
OK |
3 |
Load cycle |
GB11033 |
Heating for 5h, cooling for 3h, conductor¡¯s temperature is 95¡É,
3 cycles |
Conductor¡¯s
temperture is 95¡É.
Results refer to the following test |
As left |
4 |
Partial discharge |
GB11033 |
10pC max, at 39KV |
39kV,
¡Â
10pC |
OK |
5 |
Impulse Voltage withstand 1.2/50us¡¾10times |
GB11033 |
10 positive and 10 negative impulses
at 250KV, Flashover 1time is allowed but not including total testing
times |
10 Positive and 10 negative impulses
at 250KV, No breakdown of the combi.sample occurred at 250kV |
OK |
6 |
DC voltage withstand negative 15min |
GB11033 |
No breakdown and flashover shall
occur at 156kv |
No breakdown and flashover occurred
on the combi.sample at 156kv, 15min |
OK |
7 |
AC voltage withstand, 4h |
GB11033 |
No breakdown and flashover shall
occur at 104kv |
No breakdown and flashover occurred
on the combi.sample at 104kv, 4h |
OK |
¡¡ |