Power Cable Accessories :
  Joints for Screen Paper Rubber Insulated Cables
  6KV and 10KV

¡¡

¡¡

COMPONENTS

1. Out Protective Tubing
2. Side Sleeve
3. Metal case
4. Worm Drive Clamp
5. Earthing Plumb
6. Copper Mesh
7. Earthing Braid
8. Glass Cushion Tape
9. Belting Oil Barrier Sleeve
10. Stress Control Tubing
11. Oil-resistant Tubing
12. Red Mastic Filler
13. Inner Insulation Tubing
14. High Parmitiveity Wedge
15. Conductive Wedge
16. Yellow Void Filler
¡¡

Cables
  • The joints are designed for 1-and 3-core polymeric or rubber insulated cables.
    For Example : YJV, YJLV32, NTSC, NXSEY, NAXSEY, NXSY, NAXY

PRODUCT SPECIFICATION
¡¡

Ordering Description Type Name Cross Section (§±)
4140102090110 JSZ - 10/1x1 10KV 1-core PILC cable joint 25-50
4140102090210 JSZ - 10/1x2 70-120
4140102090310 JSZ - 10/1x3 150-240
4140102090410 JSZ - 10/1x4 300-400
4140102120110 JSZ - 10/3x1 10KV 3-core PILC cable joint 25-50
4140102120210 JSZ - 10/3x2 70-120
4140102120310 JSZ - 10/3x3 150-240
4140102120410 JSZ - 10/3x4 300-400
¡¡

Heat-shrinkable Power Cable Accessories Testing for 10KV PILC Cable
¡¡
Item
NO
property Test Requirements Results Joint
1 AC withstand for 1min GB11033 No breakdown and flashover shall occur at 45kv, 1min No breakdown and flashover occurred on the combi.sample at 45kv, 1min OK
2 Load cycle GB11033 Heating for 5h, cooling for 3h, conductor¡¯s temperature is 65¡É, 3 cycles Conductor¡¯s temperture is 65¡É. Results refer to the following test As left
3 Impulse Voltage withstand 1.2/50us¡¾10times GB11033 10 positive and 10 negative impulses at 105KV, Flashover 1time is allowed but not including total testing times No breakdown of the combi.sample occurred at 105kv OK
4 DC voltage withstand negative 15min GB11033 No breakdown and flashover shall occur at 52kv No breakdown and flashover occurred on the combi.sample at 52kv, 15min OK
5 AC voltage withstand, 4h GB11033 No breakdown and flashover shall occur at 35kv, 4h No breakdown and flashover occurred on the combi.sample at 35kv, 4h OK
6 Oil-seal up test DL413 Heating for 24h, cooling for 24h, conductor¡¯s temperature is 65¡É, Oil pressure : 100MPa Heating for 24h, cooling for 24h, conductor¡¯s temperature is 65¡É, Oil pressure : 100MPa, No leaking, No seelping OK

    
¡¡

Copyright(c)since 2003 Reliance Corp. All right reserved
1304, Kumkwang Benesta,1149-2, Jung-Dong, Wonmi-Gu,
Bucheon-city, Gyeonggi-do 420-020, KOREA