COMPONENTS

1. Red mastic Filler
2. Lug
3. Core
4. Sealing Insulation Tubing
5. Anti-tracking Tubing
6. Stress Control Tubing
7. Single-core Skirt
8. Protective Tubing

 9. Copper Binding Wire
10. Tri-core Skirt
11. Breakout
12. Yellow Void Filler
13. Worm Driver Clamp
14. Earthing Braid
15. Roll Spring

Cables
  • The terminations are designed for 1-and 3-core screen polymeric insulated cables.
    For Example : YJV, YJLV32, NTSC, N2XSEY, NA2XSEY, N2XSY, NA2XSY

PRODUCT SPECIFICATION
¡¡

Ordering Description Type Name Cross Section (§±)
4140103010110 NSY 35 / 1x1 35KV 1-core XLPE cable indoor termination 25-50
4140103010110 NSY35 / 1x2 70-120
4140103010110 NSY35 / 1x3 150-240
4140103010110 NSY35 / 1x4 300-400
4140103020110 WSY 35 / 1x1 35KV 1-core XLPE cable outdoor termination 25-50
4140103020110 WSY35 / 1x2 70-120
4140103020110 WSY35 / 1x3 150-240
4140103020110 WSY 35 / 1x4 300-400
4140103040110 NSY 35 / 3x1 35KV 3-core XLPE cable indoor termination 25-50
4140103040110 NSY35 / 3x2 70-120
4140103040110 NSY35 / 3x3 150-240
4140103040110 NSY35 / 3x4 300-400
4140103050110 WSY 35 / 3x1 35KV 3-core XLPE cable outdoor termination 25-50
4140103050110 WSY35 / 3x2 70-120
4140103050110 WSY35 / 3x3 150-240
4140103050110 WSY35 / 3x4 300-400
¡¡
The normal terminations for screen Polymeric insulated cables 20KV and 35KV supply without lugs. The normal length of the anti-tracking tubing is 800mm. If the local installation requires different length of the anti-tracking tubing and oil-resistant, we can supply.


Heat-shrinkable Power Cable Accessories Testing for 35KV XLPE Cable
¡¡
Item
NO
property Test Requirements Results Outdoor termination Indoor termination
1 AC withstand for 1min
(dry withstand)
GB11033 No breakdown and flashover shall occur at 105kv No breakdown and flashover occurred on the combi.sample at 105kv, 1min ¡¡ OK
2 AC withstand for 1min
(wet withstand)
GB11033 No breakdown and flashover shall occur at 105kv No breakdown and flashover occurred on the combi.sample at 105kv, 1min OK OK
3 Partial discharge GB11033 10pC max, at 39KV 39KV¡Â10pC OK OK
4 Load cycle GB11033 Heating for 5h, cooling for 3h, Conductor¡¯s temperature is 95¡É, 3cycles Conductor¡¯s temperture is 95¡É.Results refer to the following Test As left As left
5 Partial discharge GB11033 10pC max, at 39KV 39KV¡Â10pC OK OK
6 Impulse Voltage withstand 1.2/50us¡¾10times GB11033 10positive and 10 negative impulses at 250KV, Flashover 1time is allowed but not including total testing times 10 positive and 10 negative impulses at 250KV,No breakdown of the combi.sample occurred at 250KV OK OK
7 DC Voltage withstand, negative 15min GB11033 No breakdown and flashover shall occur at 156kv No breakdown and flashover occurred on the combi.sample at 156kv, 15min OK OK
8 AC Voltage withstand, 4h GB11033 No breakdown and flashover shall occur at 104kv No breakdown and flashover occurred on the combi.sample at 104kv, 4min OK OK

    
¡¡