Cables :
XLPE insulated power
cable for voltage up to 35KV |
|
High Voltage Lab. |
|
Brief Introduction
to XLPE Insulated Power Cable
Cross-linked polyethylene insulated power
cable not only has excellent electric, mechanical but also has
powerful resistance against chemical corrosion, heataging and
environmental stress. Its structure is simple. The permissible
maximum operating temperature is 90”. It is convenient to use and
can be laid with no restriction of different elevation.
Our XLPE cable can be produced according to our work's
specification which is equivalent IEC60502, and its some
properties required are superior to IEC60502.
We can design and manufacture special XLPE cable according to the
other standards, required by the customers.
|
Rate
Voltage
KV |
1st Class |
0.6/1 |
1.8/3 |
3.6/6 |
6/10 |
8.7/15 |
12/20 |
18/30 |
21/35 |
2nd Class |
1/1 |
3/3 |
6/6 |
8.7/10 |
12/15 |
18/20 |
- |
26/35 |
Number of core |
Cross section П |
1 Core |
|
1.5~800 |
25~800 |
25~1200 |
25~1200 |
35~1200 |
50~1200 |
50~1200 |
50~1200 |
2 Core |
|
1.5~185 |
25~185 |
|
|
|
|
|
|
3 Core |
|
1.5~400 |
25~400 |
25~400 |
25~400 |
35~400 |
50~400 |
50~400 |
50~400 |
(3+1,4)
4 Core |
|
2.5~400 |
25~400 |
|
|
|
|
|
|
(4+1,3_2,5)
5 Core |
|
2.5~400 |
25~400 |
|
|
|
|
|
|
The cables in the 1st class
are available to the condition of the earth fault time within 1
minute. The cables in the 2nd class are available to earth fault
time not exceeding 2 hours generally, maximum time is not more than 8
hours
XLPE Cable's Type
and Main Application
|
Type |
Description |
main Application |
Cu core |
Al core |
YJV
or
YJY |
YJLV
or
YJLY |
XLPE inslated,
PVC or PE sheathed power cable |
For laying
indoor, tunnel, canal and underground. Unable to bear external
mechanical forces, but bear the traction force during laid |
YJV22
or
YJV23 |
YJLV22
or
YJV23 |
XLPE insulated,
steel tape armoured, PVC or PE sheathed power cable |
For laying
indoor, tunnel, canal and underground, Able to bear external
mechanical forces, but unable to bear large pulling force |
YJV32
or
YJV33 |
YJLV32
or
YJLV33 |
XLPE insulated,
fine steel wire armoured, PVC or PE sheathed power cable |
For laying in
shaft, with large difference of level, able to bear external
mechanical forces and moderate pulling force |
YJV42
or
YJV43 |
YJLV42
or
YJLV43 |
XLPE insulated,
thick steel wire armoured, PVC or PE sheathed power cable |
Able to bear
positive pressure and pulling force |
Note : "ZR-" undudes
three kinds (A,B,C) of flame retardant cables, respectively
indicated in "ZRA-", "ZRB-" or "ZRC-", For example, "ZRB-JYV",
"ZRA-YJV22"
Cable Main
Technical Characteristics
: Conductor resistance of finished cable at 20” per kilometer is
not more than the following
values.
|
Normal
cross-section П |
1.5 |
2.5 |
4 |
6 |
10 |
16 |
25 |
35 |
50 |
70 |
Cu Core |
12.1 |
7.41 |
4.61 |
3.08 |
1.83 |
1.15 |
0.727 |
0.524 |
0.387 |
0.268 |
Al Core |
18.1 |
12.1 |
7.41 |
4.61 |
3.08 |
1.91 |
1.20 |
0.868 |
0.641 |
0.443 |
Normal
cross-section П |
95 |
120 |
150 |
185 |
240 |
300 |
400 |
500 |
630 |
800 |
Cu Core |
0.193 |
0.153 |
0.124 |
0.0991 |
0.0754 |
0.0601 |
0.0470 |
0.0366 |
0.0283 |
0.0221 |
Al Core |
0.320 |
0.253 |
0.206 |
0.164 |
0.125 |
0.100 |
0.0778 |
0.0605 |
0.0469 |
0.0367 |
: B and C.
Voltage Test and Partial Discharge Test |
Rated Voltage Uo/Ukv
Item |
0.6/1 |
1/1 |
1.8/3 |
3/3 |
3.6/6 |
6/6
6/10 |
8.7/10
8.7/15 |
12/20 |
18/20
18/30 |
21/35 |
26/35 |
B |
Voltage Test |
Test Voltage |
3.5 |
4.5 |
6.5 |
9.5 |
11 |
15 |
22 |
30 |
45 |
53 |
65 |
Test Time |
5 |
5 |
5 |
5 |
5 |
5 |
5 |
5 |
5 |
5 |
5 |
C |
Test
of partial Discharge |
Test Voltage |
|
|
|
|
6 |
9 |
13 |
18 |
27 |
32 |
39 |
Discharge
Capacity |
|
|
|
|
20 |
20 |
20 |
20 |
20 |
10 |
10 |
|