Power Cable Accessories :
  Transition Joints for Screen polymeric Insulated Cables to
  screen paper Insulated 20KV and 35KV

¡¡

¡¡

COMPONENTS

1. Connector
2. Yellow Void Filler
3. Oil-resistant Tubing
4. Semi-conductive Tubing
5. Oil-resistant Filler
6. Conductive Breakout
7. Grey Mastic
8. Stress Control Tubing
9. Inner Insulation Tubing
10. Insulation/Conductive Tubing
11. Inner Protective Tubing
     (compression sleeve)
12. Metal Case
13. Side Sleeve
14. Stress Control Wedge
15. Copper Mesh
16. Roll Spring
17. Earthing Braid
18. Worm Driver Clamp
19. Outer Protective Tubing

Cables
  • The joints are designed for 1-and 3-core screened paper with one metal sheath for phase to screened 1-or-3-core polymeric insulated cables 35KV
    For Example : YJV, YJLV32, NTSC, N2XSEY, NA2XSEY, N2XSY, NA2XSYm ZQFD41, ZQFD20, NAEKEBA, NEKENA, NEKEBY

PRODUCT SPECIFICATION
¡¡

Ordering Description Type Name Cross Section (§±)
4140103130110 JSYZ - 35/1x01 35KV 1-core XLPE-PILC cable joint 50-95
4140103130210 JSYZ - 35/1x02 120-185
4140103130310 JSYZ - 35/1x03 240-400
4140103140110 JSYZ - 35/3x01 35KV 3-core XLPE-PILC cable joint 50-95
4140103140210 JSYZ - 35/3x02 120-185
4140103140310 JSYZ - 35/3x03 240-400
¡¡

Heat-shrinkable Power Cable Accessories Testing for 10KV PILC Cable
¡¡
Item
NO
property Test Requirements Results Joint
1 AC withstand for 1min GB11033 No breakdown and flashover shall occur at 105kv No breakdown and flashover occurred on the combi.sample at 105kv, 1min OK
2 Load cycle GB11033 Heating for 5h, cooling for 3h, conductor¡¯s temperature is 65¡É, 3 cycles Conductor¡¯s temperture is 65¡É. Results refer to the following test As lest
3 Impulse Voltage withstand 1.2/50us¡¾10times GB11033 10 positive and 10 negative impulses at 250KV, Flashover 1time is allowed but not including Total testing times 10 Positive and 10 negative impulses at 250KV, No breakdown of the combi.sample occurred at 250kV OK
4 DC voltage withstand negative 15min GB11033 No breakdown and flashover shall occur at 156kv No breakdown and flashover occurred on the combi.sample at 156kv, 15min OK
5 AC voltage withstand, 4h GB11033 No breakdown and flashover shall occur at 104kv No breakdown and flashover occurred on the combi.sample at 104kv, 4h OK
6 Oil-seal up test DL413 Heating for 24h, cooling for 24h, conductor¡¯s temperature is 65¡É, oil pressure : 100MPa Heating for 24h, cooling for 24h, conductor¡¯s temperature is 65¡É, oil pressure : 100MPa, No Leaking, No seeping OK

    
¡¡