Power Cable Accessories :
  Joints for Paper Insulated Cables 1KV

¡¡

¡¡

COMPONENTS

1. Insulation Sleeve
2. Metallic Protection Cage
3. Oil Barrier Sleeve
4. Inner Protection Sleeve
5. Out Jacketing Sleeve
6. Armour Continuity Connection
7. Worm Drive Clamp
8. Earthing Plumb

Cables
  • The joints are designed for 3-and 4-core paper insulated cables.
    For Example : ZQD, ZQ, ZQD22, NAYA, NAYBA, NAKBA

PRODUCT SPECIFICATION
¡¡

Ordering Description Type Name Cross Section (§±)
4140101180110 JSZ - 1/3x0 1KV 3-core PILC cable joint 10-16
4140101180210 JSZ - 1/3x1 25-50
4140101180310 JSZ - 1/3x2 70-120
4140101180410 JSZ - 1/3x3 150-240
4140101180510 JSZ - 1/3x4 300-400
4140101200110 JSZ - 1/4x0 1KV 4-core PILC cable joint 10-16
4140101200210 JSZ - 1/4x1 25-50
4140101200310 JSZ - 1/4x2 70-120
4140101200410 JSZ - 1/4x3 150-240
4140101200510 JSZ - 1/4x4 300-400
4140101122110 JSZ - 1/4x0 1KV 4-core (3+1) PILC cable joint 10-16
4140101122210 JSZ - 1/4x1 25-50
4140101122310 JSZ - 1/4x2 70-120
4140101122410 JSZ - 1/4x3 150-240
4140101122510 JSZ - 1/4x4 300-400
¡¡

Heat-shrinkable Power Cable Accessories Testing for 1KV XLPE Cable
¡¡
Item
NO
property Test Requirements Results Joint
1 AC withstand for 15min IEC60060 No breakdown and flashover shall occur at 4kv No breakdown and flashover occurred on the combi.sample at 4kv OK
2 mpulse Voltage withstand IEC60060
IEC60230
10positive and 10 negative impulses at 8KV No breakdown and flashover occurred on the combi.sample at 19kv OK
3 Thermal short-circuit test VDE0278 No transfigure and welding shall occur on all parts at 17.7KA, 1s No transfigure and welding occurred on all parts at 17.7KA,1.03s;17.8KA,1.03s OK
4 DC negative polarity voltage withstand for 5min IEC60060 No breakdown and flashover shall occur at 15kv No breakdown and flashover occurred on the combi.sample at 15kv OK
5 AC Voltage withstand, 4h GB11033
GB5589
2.4KV/4h 2.4KV/4h OK
6 Oil-seal up test DL413 Heating for 24h, cooling for 24h, Conductor¡¯s temperature is 65¡É, oil pressure : 100MPa Heating for 24h, cooling for 24h, Conductor¡¯s temperature is 65¡É, oil pressure : 100MPa,No leaking, No seeping OK

    
¡¡