Power Cable Accessories :
  Terminations for Polymeric or Rubber Insulated Cables
  6KV and 10KV (indoor or outdoor)

¡¡

¡¡

¡¡

COMPONENTS

1. Red mastic Filler
2. Lug
3. Core
4. Sealing Insulation Tubing
5. Anti-tracking Tubing
6. Stress Control Tubing
7. Single-core Skirt
8. Protective Tubing

 9. Copper Binding Wire
10. Tri-core Skirt
11. Breakout
12. Yellow Void Filler
13. Worm Driver Clamp
14. Earthing Braid
15. Roll Spring

Cables
  • The terminations are designed for 1-and 3-core polymeric or rubber insulated cables.
    For Example : YJV, YJLV32, NTSC, N2XSEY, NA2XSEY, N2XSY, NA2XSY

PRODUCT SPECIFICATION
¡¡

Ordering Description Type Name Cross Section (§±)
4140102010110 NSY – 10 / 1x1 10KV 1-core XLPE cable indoor termination 25-50
4140102010210 NSY – 10 / 1x2 70-120
4140102010310 NSY – 10 / 1x3 150-240
4140102010410 NSY – 10 / 1x4 300-400
4140102020110 WSY – 10 / 1x1 10KV 1-core XLPE cable outdoor termination 25-50
4140102020210 WSY – 10 / 1x2 70-120
4140102020310 WSY – 10 / 1x3 150-240
4140102020410 WSY – 10 / 1x4 300-400
4140102040110 NSY – 10 / 3x1 10KV 3-core XLPE cable indoor termination 25-50
4140102040210 NSY – 10 / 3x2 70-120
4140102040310 NSY – 10 / 3x3 150-240
4140102040410 NSY – 10 / 3x4 300-400
4140102050110 WSY – 10 / 3x1 10KV 3-core XLPE cable outdoor termination 25-50
4140102050210 WSY – 10 / 3x2 70-120
4140102050310 WSY – 10 / 3x3 150-240
4140102050410 WSY – 10 / 3x4 300-400
¡¡
The normal terminations for screen polymeric or rubber insulated cables 6KV and 10KV supply without lugs. The normal length of the anti-tracking tubing is 650mm. If the local installation requires different length of the anti-tracking tubing, we can supply.


Heat-shrinkable Power Cable Accessories Testing for 10KV XLPE Cable
¡¡
Item
NO
property Test Requirements Results Outdoor termination Indoor termination
1 AC withstand for 1min
(dry withstand)
JB8144 No breakdown and flashover shall occur at 45kv No breakdown and flashover occurred on the combi.sample at 45kv, 1min ¡¡ OK
2 AC withstand for 1min
(wet withstand)
JB8144 No breakdown and flashover shall occur at 45kv No breakdown and flashover occurred on the combi.sample at 45kv, 1min OK ¡¡
3 Partial discharge JB/T8138.3 3pC max. at 9KV a,b,c < 3pc OK OK
4 Partial discharge JB/T8138.3 20pC max. at 13KV a,b,c < 3pc OK OK
5 Load cycle JB/T8138.3 Heating for 5h, cooling for 3h. Conductor¡¯s temperature is90-95¡É 3Cycles Conductor¡¯s temperture is 95¡É.Results refer to the following Test As left As left
6 Partial discharge JB/T8138.3 3pC max. at 9KV a,b,c < 3pc OK OK
7 Partial discharge JB/T8138.3 20pC max. at 13KV a,b,c < 3pc OK OK
8 Impulse Voltage withstand 1.2/50us ¡¾10times JB/T8138.1
GB/T16927
10 positive and 10 negative impulses at 105KV, No breakdown No breakdown of the combi.sample occurred at 105KV OK OK
9 DC Voltage withstand negative 15min JB/T8138.1 No breakdown and flashover shall occur at 52KV No breakdown of the combi.sample occurred on the combi.sample at 52KV, 15min OK OK
10 AC Voltage withstand, 4h JB/T8144.1 No breakdown shall occur at 35KV,4h No breakdown occurred on the combi.sample at 35KV,4h OK OK
11 Sealing test DL413 Heating for 5h,cooling for 3h, conductor¡¯s temperature us 90-95¡É in water bath, 9cycles Heating for 5h, cooling for 3h. Conductor¡¯s temperature is 90-95¡É in water bath, 9 cycles, Result refer to the following Test As left As left
12 AC Voltage withstand, 15min JB/T8144.1 No breakdown and flashover shall occur at 25KV No breakdown and flashover occurred on the combi.sample at 25KV, 15min OK OK

    
¡¡