Power Cable
Accessories
:
Terminations for
Polymeric or Rubber Insulated Cables
6KV and 10KV (indoor or outdoor) |
¡¡ ¡¡ |
Ordering
Description |
Type |
Name |
Cross Section (§±) |
4140102010110 |
NSY
– 10 /
1x1 |
10KV
1-core
XLPE
cable indoor termination |
25-50 |
4140102010210 |
NSY
– 10 /
1x2 |
70-120 |
4140102010310 |
NSY
– 10 /
1x3 |
150-240 |
4140102010410 |
NSY
– 10 /
1x4 |
300-400 |
4140102020110 |
WSY
– 10 /
1x1 |
10KV
1-core
XLPE
cable outdoor termination |
25-50 |
4140102020210 |
WSY
– 10 /
1x2 |
70-120 |
4140102020310 |
WSY
– 10 /
1x3 |
150-240 |
4140102020410 |
WSY
– 10 /
1x4 |
300-400 |
4140102040110 |
NSY
– 10 /
3x1 |
10KV
3-core
XLPE
cable indoor termination |
25-50 |
4140102040210 |
NSY
– 10 /
3x2 |
70-120 |
4140102040310 |
NSY
– 10 /
3x3 |
150-240 |
4140102040410 |
NSY
– 10 /
3x4 |
300-400 |
4140102050110 |
WSY
– 10 /
3x1 |
10KV
3-core
XLPE
cable outdoor termination |
25-50 |
4140102050210 |
WSY
– 10 /
3x2 |
70-120 |
4140102050310 |
WSY
– 10 /
3x3 |
150-240 |
4140102050410 |
WSY
– 10 /
3x4 |
300-400 |
¡¡
The normal terminations for
screen polymeric or rubber insulated cables 6KV and 10KV supply
without lugs. The normal length of the anti-tracking tubing is
650mm. If the local installation requires different length of the
anti-tracking tubing, we can supply.
Heat-shrinkable
Power Cable Accessories Testing for 10KV XLPE Cable
¡¡ |
Item
NO |
property |
Test |
Requirements |
Results |
Outdoor termination |
Indoor termination |
1 |
AC withstand for 1min
(dry withstand) |
JB8144 |
No breakdown and flashover shall
occur at 45kv |
No breakdown and flashover occurred
on the combi.sample at 45kv, 1min |
¡¡ |
OK |
2 |
AC withstand for 1min
(wet withstand) |
JB8144 |
No breakdown and flashover shall
occur at 45kv |
No breakdown and flashover occurred
on the combi.sample at 45kv, 1min |
OK |
¡¡ |
3 |
Partial discharge |
JB/T8138.3 |
3pC max. at 9KV |
a,b,c < 3pc |
OK |
OK |
4 |
Partial discharge |
JB/T8138.3 |
20pC max. at 13KV |
a,b,c < 3pc |
OK |
OK |
5 |
Load cycle |
JB/T8138.3 |
Heating for 5h, cooling for 3h. Conductor¡¯s temperature is90-95¡É
3Cycles |
Conductor¡¯s
temperture is 95¡É.Results
refer to the following Test |
As left |
As left |
6 |
Partial discharge |
JB/T8138.3 |
3pC max. at 9KV |
a,b,c < 3pc |
OK |
OK |
7 |
Partial discharge |
JB/T8138.3 |
20pC max. at 13KV |
a,b,c < 3pc |
OK |
OK |
8 |
Impulse Voltage withstand 1.2/50us
¡¾10times |
JB/T8138.1
GB/T16927 |
10 positive and 10 negative impulses
at 105KV, No breakdown |
No breakdown of the combi.sample
occurred at 105KV |
OK |
OK |
9 |
DC Voltage withstand negative 15min |
JB/T8138.1 |
No breakdown and flashover shall
occur at 52KV |
No breakdown of the combi.sample
occurred on the combi.sample at 52KV, 15min |
OK |
OK |
10 |
AC Voltage withstand, 4h |
JB/T8144.1 |
No breakdown shall occur at 35KV,4h |
No breakdown occurred on the
combi.sample at 35KV,4h |
OK |
OK |
11 |
Sealing test |
DL413 |
Heating for 5h,cooling for 3h, conductor¡¯s temperature us 90-95¡É
in water bath, 9cycles |
Heating for 5h, cooling for 3h. Conductor¡¯s temperature is 90-95¡É
in water bath, 9 cycles, Result refer to the following Test |
As left |
As left |
12 |
AC Voltage withstand, 15min |
JB/T8144.1 |
No breakdown and flashover shall
occur at 25KV |
No breakdown and flashover occurred
on the combi.sample at 25KV, 15min |
OK |
OK |
¡¡ |